説明
Product Specification
- Type: Integrated
- Certification No. COX-14EN
Main Chasis & Container
- External Dimentions (H×W×D)mm: 1,160×400×300
- Weight: Approx. 86kg
- Fire Extinguishing Agent: Carbon Dioxide ( CO2 )
- Weight of the Fire Extinguishing Agent: 14kg
- Coating Specifications: Coating Color : Red Melamine Baking Finish, Japaning
- Material: Steel ( SPCC ) t=1.6mm
- Operating Temperature Range: 0℃~+40℃
Control Function
- Input Supply Voltage Range: 100V, 110V, 200V, 220V, AC 50/60Hz ( With Each Voltage Terminal )
- Power Cunsumption: 24VA Max.
- Operation Circuit Voltage: 24V DC
- Sensor Input Circuit: 2 System ( AND / OR Operation Selection System )
- Push Button for Start-Up: Red Push Button ( With Breaking Acrylic Plate )
- Reset Button: White Push Button
- Automatic/Manual Operations Selector Switch: The Fire
- Extinguisher can be Operated with a Sensor Input Signal in the Automatic Mode
- Alarm Buzzer: Electronic Buzzer ( Continuous Sound in Case of Fire、Intermittent Sound in Case of Abnormal Condition )
- Buzzer Stop Switch: Stops the Intermittent Sound in Case of Abnormal Condition ( The Continuous Sound in Case of a Fire Cannot be Stopped )
- Power Indicator Lamp: Green LED
- Auto Indicator Lamp: Green LED ( Light Up in the Auto Mode )
- Fire Indicator Lamp: Red LED ( Flashing in Case of Fire )
- Discharge Indicator Lamp: Red LED ( Flashing when Discharge)
- Fault Indicator Lamp: Yellow LED ( Flashing at start-up unit failure, sensor wiring line suspended )
- Barn-out Indicator Lamp: Red LED ( Flashing at Sensor Wiring Line Suspended )
- Unit Failure Indicator Lamp: Red LED ( Flashing When the Start-Up Unit Connector is not Connected Yet )
- Reduced Pressure Indicator Lamp: Red LED ( Flashing When the Fire Extinguishing Container Inner Pressure Drops )
- Buzzer Stop Indicator Lamp: Red LED ( Flashing at Buzzer Stop)
- Fire Annunciating Contact: Contact c×1( Contact Switches at Sensor Alarm )
- Machine Stop Contact: Contact c×1, Contact a×1, Contact b×1( Contact Switches at AC Power Down )
- Power Failure Annunciating Contact: Contact c×1( Contact Switches at Discharge )
- Fault Annunciating Contact: Contact c×1( Contact Switches at Fault, except Start-Up Unit Connection Fault )
- Automatic/Manual Annunciating Contact: Contact c×1( Manual Mode B-B2 is Closed, Auto Mode B-B1 is Closed )
- Contact Specification: Contact Capacity : 60W/125VA Max.
- Maximum Current: 1A Maximum Voltage: 250V AC/200V DC
- Battery: Ni-Cd battery/24V DC/0.45Ah/5hours
- Timer: Delayable up to 10 seconds
- Remote start (Manual Release): Possible to actuate by remote push button