Inverter SANUPS D11A
Parallel Operation Cabinet with bypass circuit


Inverter SANUPS D11A
Parallel Operation Cabinet with bypass circuit

Description

Specifications

Model No.

1. PD-D11AB13

  • Number of inverter units:2/ 3
  • Device configuration:
    N-unit configuration/ N+1-unit configuration/ N-unit configuration/ N+1-unit configuration
  • DC input rated voltage: 48 V
  • DC input maximum input current : 58.5 A/ 30.4 A/ 87.6 A/ 59.5 A
  • AC input rated voltage: 100/120 V
  • AC input maximum input current: 20.4 A/ 10.3 A/ 30.6 A/ 20.5 A
  • AC output rated voltage: 100/120 V
  • AC output capacity: 2 kW/ 1 kW/ 3 kW/ 2 kW
  • Remarks: with bypass circuit

2. PD-D11AB13US

  • Number of inverter units:2/ 3
  • Device configuration:
    N-unit configuration/ N+1-unit configuration/ N-unit configuration/ N+1-unit configuration
  • DC input rated voltage: 48 V
  • DC input maximum input current : 58.5 A/ 30.4 A/ 87.6 A/ 59.5 A
  • AC input rated voltage: 100/120 V
  • AC input maximum input current: 20.4 A/ 10.3 A/ 30.6 A/ 20.5 A
  • AC output rated voltage: 100/120 V
  • AC output capacity: 2 kW/ 1 kW/ 3 kW/ 2 kW
  • Remarks: with bypass circuit / UL certified unit
  • 3. PD-D11AB15

    • Number of inverter units:
    • 3/ 4/ 5

    • Device configuration:N-unit configuration/ N+1-unit configuration/ N-unit configuration/ N+1-unit configuration/
      N-unit configuration/ N+1-unit configuration
    • DC input rated voltage : 48 V
    • DC input maximum input current: 87.6 A/ 59.5 A/ 116.8 A/ 88.7 A/ 146.0 A/ 117.9 A
    • AC input rated voltage: 100/120 V
    • AC input maximum input current: 30.6 A/ 20.5 A/ 40.8 A/ 30.7 A/ 51.0 A/ 40.9 A
    • AC output rated voltage: 100/120 V
    • AC output capacity: 3 kW/ 2 kW/ 4 kW/ 3 kW/ 5 kW/ 4 kW
    • Remarks: with bypass circuit
    • 4. PD-D11AB15US

    • Number of inverter units:
    • 3/ 4/ 5

    • Device configuration:N-unit configuration/ N+1-unit configuration/ N-unit configuration/ N+1-unit configuration/
      N-unit configuration/ N+1-unit configuration
    • DC input rated voltage : 48 V
    • DC input maximum input current: 87.6 A/ 59.5 A/ 116.8 A/ 88.7 A/ 146.0 A/ 117.9 A
    • AC input rated voltage: 100/120 V
    • AC input maximum input current: 30.6 A/ 20.5 A/ 40.8 A/ 30.7 A/ 51.0 A/ 40.9 A
    • AC output rated voltage: 100/120 V
    • AC output capacity: 3 kW/ 2 kW/ 4 kW/ 3 kW/ 5 kW/ 4 kW
    • Remarks: with bypass circuit / UL certified unit
    • 5. PD-D11AB16

    • Number of inverter units:
    • 5/ 6

    • Device configuration: N-unit configuration/ N+1-unit configuration/ N+1-unit configuration/ N-unit configuration/
      N+1-unit configuration
    • DC input rated voltage : 48 V
    • DC input maximum input current: 146.0 A/ 117.9 A/ 175.1 A/ 147.0 A
    • AC input rated voltage: 100/120 V
    • AC input maximum input current: 51.0 A/ 40.9 A/ 61.2 A/ 51.1 A
    • AC output rated voltage: 100/120 V
    • AC output capacity: 5 kW, 4 kW, 6 kW, 5 kW
    • Remarks: with bypass circuit
    • 6. PD-D11AB16US

      • Number of inverter units:
      • 5/ 6

      • Device configuration: N-unit configuration/ N+1-unit configuration/ N-unit configuration/ N+1-unit configuration
      • DC input rated voltage : 48 V
      • DC input maximum input current: 146.0 A/ 117.9 A/ 175.1 A/ 147.0 A
      • AC input rated voltage: 100/120 V
      • AC input maximum input current: 51.0 A/ 40.9 A/ 61.2 A/ 51.1 A
      • AC output rated voltage: 100/120 V
      • AC output capacity: 5 kW/ 4 kW/ 6 kW/ 5 kW
      • Remarks: with bypass circuit / UL certified unit

        Features

        1.High Efficiency

        86.6% (maximum) high efficiency.
        It helps to conserve energy and reduce power charges.

        2.Increasing the Reliability of Power Supply

        The output is a pure sine wave.
        D11A can perform parallel redundant operation.
        A redundant configuration of N+1 units with a backup unit increases the reliability
        of inverter power supply.
        Totally independent control with high reliability has been realised.

        3.Bypass Function for security

        Even if a power failure occurs, switching to the AC input bypass circuit keeps power supply stable.

        4.Simple to Add Units

        Up to 6 units (6 kVA) can be added.
        In redundant operation, a unit can be replaced without the need to shut down its power supply.
        A unit can be installed easily in the parallel operation cabinet from the front.