CPX-REN2 CABINEX-EN2

CPX-REN2 CABINEX-EN2

£333.00

Below is a typical installation drawing for Cleaning Equipment.
Explanation of each part of the Cabinex system.
(1) CABINEX Body・Main : to contain CO 2 Cylinder and Control Panel. It should be selected in accordance with the volume of extinguishing chemical agent required.
(2) CABINEX Body・Sub : to contain only CO 2 Cylinder which is discharged together with Main’s simultaneously.
(3) TH Sensor : Heat Detector at 70℃. Hatsuta’s original sensor.
(4) Infrared Sensor : Flame Detector. Hatsuta’s original sensor.
(5) Nozzle : Total flooding system.

 

Description

Product Specification

  • Type: Separate Type Control Unit
  • Certification No. CPX-REN2

Main Chasis & Container

  • External Dimentions (H×W×D)mm: 340×280×90
  • Weight: Approx. 6kg
  • Fire Extinguishing Agent: Carbon Dioxide ( CO2 )
  • Coating Specifications: Coating Color : Red Melamine Baking Finish, Japaning
  • Material: Steel ( SPCC ) t=1.6mm
  • Operating Temperature Range: 0℃~+40℃

Control Function

  • Input Supply Voltage Range: 100V, 110V, 200V, 220V, AC 50/60Hz ( With Each Voltage Terminal )
  • Power Cunsumption: 24VA Max.
  • Operation Circuit Voltage: 24V DC
  • Sensor Input Circuit: 2 System ( AND / OR Operation Selection System )
  • Push Button for Start-Up: Red Push Button ( With Breaking Acrylic Plate )
  • Reset Button: White Push Button
  • Automatic/Manual Operations Selector Switch: The Fire Extinguisher can be Operated with a Sensor Input Signal in the Automatic Mode
  • Alarm Buzzer: Electronic Buzzer ( Continuous Sound in Case of Fire、Intermittent Sound in Case of Abnormal Condition )
  • Buzzer Stop Switch: Stops the Intermittent Sound in Case of Abnormal Condition ( The Continuous Sound in Case of a Fire Cannot be Stopped )
  • Power Indicator Lamp: Green LED
  • Auto Indicator Lamp: Green LED ( Light Up in the Auto Mode )
  • Fire Indicator Lamp: Red LED ( Flashing in Case of Fire )
  • Discharge Indicator Lamp: Red LED ( Flashing when Discharge)
  • Fault Indicator Lamp: Yellow LED ( Flashing at start-up unit failure, sensor wiring line suspended )
  • Barn-out Indicator Lamp: Red LED ( Flashing at Sensor Wiring Line Suspended )
  • Unit Failure Indicator Lamp: Red LED ( Flashing When the Start-Up Unit Connector is not Connected Yet )
  • Reduced Pressure Indicator Lamp: Red LED ( Flashing When the Fire Extinguishing Container Inner Pressure Drops )
  • Buzzer Stop Indicator Lamp: Red LED ( Flashing at Buzzer Stop)
  • Fire Annunciating Contact: Contact c×1( Contact Switches at Sensor Alarm )
  • Machine Stop Contact: Contact c×1, Contact a×1, Contact b×1( Contact Switches at AC Power Down )
  • Power Failure Annunciating Contact: Contact c×1( Contact Switches at Discharge )
  • Fault Annunciating Contact: Contact c×1( Contact Switches at Fault, except Start-Up Unit Connection Fault )
  • Automatic/Manual Annunciating Contact: Contact c×1( Manual Mode B-B2 is Closed, Auto Mode B-B1 is Closed )
  • Contact Specification: Contact Capacity : 60W/125VA Max.
  • Maximum Current: 1A Maximum Voltage: 250V AC/200V DC
  • Battery: Ni-Cd battery/24V DC/0.45Ah/5hours
  • Timer: Delayable up to 10 seconds
  • Remote start (Manual Release): Possible to actuate by remote push button